ComPact 2400 48 AC/DC
Input: 120 / 230 VAC, 50 / 60 / 400 HZ
Output: 20 – 65 VDC, 40 A, 2400 W
Part Number: P600610
The input current of ComPact is power factor corrected and designed for optimum utilisation of weak power sources such as portable generators. The efficiency is very high due to soft switching technology. ComPact can operate stand alone or be mounted in 19’’ rack system.
The RS-485 bus can be used for control, monitoring and setup. Detailed status and statistics can be retrieved. The bus is also used for interconnecting multiple units in a redundant or parallel system. The signal connectors provide several signals in addition to the RS485 bus: alarm relay outputs and input for battery temperature sensor. Temperature compensated charging ensures full battery capacity over the entire temperature range. ComPact can be configured to charge different battery technologies such as Li-Ion, LiPo, lithium iron phosphate and lead-acid. ComPact can be software configured according to customer specification. The firmware is user upgradeable for future battery technologies and facilities. ComPact is protected from overvoltage, overcurrent, short circuit, reversed polarity and over temperature.
REQUEST A QUOTE
Input Voltage | 99 – 276 VAC |
---|---|
Power Factor -Load: ≥ 50%, Vin: 50/60 Hz |
Typical 0.99 |
Input Current -Load: 2400 W -Vin: 50/60 Hz |
Vin: 99 VAC – ≤ 29 A Vin: 120 VAC – ≤ 23 A Vin: 230 VAC – ≤ 12 A |
Total Harmonic Distortion -Load: 2400 W, VAC: 50/60 Hz |
≤ 6% |
Efficiency -Load: 56 VDC, 40 A |
Vin: 120 VAC – ≥ 88% Vin: 230 VAC – ≥ 90% |
Default Output Voltage | 48.0 VDC |
Adjustable Output voltage | 20 – 65 VDC |
Default Output Current Limit | 42 A |
Adjustable Current Limit | 3 – 42 A |
Short Circuit Current | ≤ setting of current limiter + 1 A |
Load Sharing | ≤ 2 A deviation |
Load Regulation | Typical: 50 mV |
Line Regulation | Negligible |
Safety | CE Marked |
Over Temperature | The unit is protected from over temperature by derating the output current. It shuts down if the temperature continues to rise. The unit automatically starts up again when the temperature drops. |
---|---|
Input Circuit Breaker | The input circuit breaker is for failure protection and is also used as an ON/OFF switch. |
Alarms | Status signals are fed to separate potential outputs, and are indicated in separate LEDs. |
Display | The display can be toggled between output voltage, output current and alarm/error codes. |
Input Voltage | When the input voltage is below the safe operating range, the converter is shut off. When the voltage returns, the converter is turned on again. |
Connectors | AC input: 97-3102E-16-10P-PCC-622 Amphenol or similar DC output: 97B-3102E-22-22S-622 Amphenol or similar Alarm 1: Binder 09-0404-30-02 Alarm 2: Binder 09-0412-30-04 NTC/COM: 2 pieces. Binder 09-0416-30-05 |
Grounding | Available in the front |
Acoustic Noise | At ambient temperatures below 45°C the acoustic noise 45 dBA |
Frequency | 45 – 430 Hz |
Cooling | Forced air by temperature controlled fan |